7. Use the navigation keys to scroll to parameter
group Q2 Quick Setup and press [OK].
8. Select language and press [OK]. Then enter the
motor data in parameters 1-20/1-21 through 1-25.
The information can be found on the motor
nameplate.
1-20 Motor Power [kW] or 1-21 Motor
Power [HP]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
130BT772.10
Q2
0.0 Hz 0.00kW 1(1)
Motor Setup
1 - 21 Motor Power [kW]
4.0 kW
9. A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave 5-12 Terminal 27 Digital Input at factory
default. Otherwise select No Operation. For
adjustable frequency drives with an optional
Danfoss bypass, no jumper wire is required.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
12.
3-41 Ramp 1 Ramp-up Time
13.
3-42 Ramp 1 Ramp-down Time
14.
3-13 Reference Site. Linked to Hand/Auto* Local
Remote.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
3.4
Automatic Motor Adaptation
Automatic motor adaptation (AMA) is a test procedure that
measures the electrical characteristics of the motor to
optimize compatibility between the Adjustable frequency
drive and the motor.
The Adjustable frequency drive builds a
mathematical model of the motor for regulating
output motor current. The procedure also tests
the input phase balance of electrical power. It
compares the motor characteristics with the data
entered in parameters 1-20 to 1-25.
It does not cause the motor to run or harm to
the motor
Some motors may be unable to run the complete
version of the test. In that case, select Enable
reduced AMA
If an output filter is connected to the motor,
select Enable reduced AMA
If warnings or alarms occur, see 8 Warnings and
Alarms
Run this procedure on a cold motor for best
results
To run AMA
1. Press [Main Menu] to access parameters.
2.
Scroll to parameter group 1-** Load and Motor.
3. Press [OK].
4.
Scroll to parameter group 1-2* Motor Data.
5. Press [OK].
6.
Scroll to 1-29 Automatic Motor Adaptation (AMA).
7. Press [OK].
8.
Select Enable complete AMA.
9. Press [OK].
10. Follow on-screen instructions.
11. The test will run automatically and indicate when
it is complete.
Start-up and Functional Tes...
VLT
®
AutomationDrive Instruction
Manual
3-4 MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
33

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 303 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 303
CategoryDC Drives
LanguageEnglish

Related product manuals