Select the display output for terminal 27.
N O T I C E
This option is only available with software version 48.XX.
Actual speed reference after the ramp. Use this output as master signal for speed synchroni-
zation of follower drives. The reference is set in parameter 16-48 Speed Ref. After Ramp [RPM].
N O T I C E
This option is only available with software version 48.XX.
Virtual master signal for controlling the speed or position of the followers.
Parameter 5-62 Pulse Output Max Freq #27
Table 376: Parameter 5-62 Pulse Output Max Freq #27
5-62 Pulse Output Max Freq #27
Default value: Size related
Parameter type: Range, 0 - 110000 Hz
Change during operation: True
Set the maximum frequency for terminal 27 corresponding to the output variable selected in parameter 5-60 Terminal 27 Pulse Out-
put Variable.
AU275636650261en-000101 / 130R0334222 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide