Page #296 background imageLoading...
Page #296 background image
Option
Name
Description
[3664]
Terminal X49/11 bus control
[4029]
B-EMF protection log readout
[4280]
Safe option status
[4282]
Safe control word
[4283]
Safe status word
[4285]
Active safe func.
[4287]
Time until manual test
Parameter 8-42 PCD Write Configuration
Table 520: Parameter 8-42 PCD Write Configuration
8-42 PCD Write Configuration
Default value: Size related
Parameter type: Range, 0 - 9999, Array [64]
Setup: 2 setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Select the parameters to be assigned to the telegrams of the PCD. The number of available PCDs depends on the telegram type. The
values in the PCDs are then written to the selected parameters as data values.
Parameter 8-43 PCD Read Configuration
Table 521: Parameter 8-43 PCD Read Configuration
8-43 PCD Read Configuration
Default value: Size related
Parameter type: Range, 0 - 9999, Array [64]
Setup: 2 setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the telegram type.
PCDs contain the actual data values of the selected parameters.
Block Transfer Mode (BTM)
When Block Transfer Mode (BTM) is enabled, the parameters are written into a temporary buffer in the drive via the fieldbus. After
wiring all the required parameters to the drive in BTM mode, a Commit command is sent to the drive. The drive ensures correct
adaptation of the parameters.
Parameter 8-45 BTM Transaction Command
Table 522: Parameter 8-45 BTM Transaction Command
8-45 BTM Transaction Command
Default value: [0] Off
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Option
Name
Description
[0]*
Off
[1]
Write to active setup
AU275636650261en-000101 / 130R0334296 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT CANopen MCA 105

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CANopen MCA 105 and is the answer not in the manual?

Danfoss VLT CANopen MCA 105 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CANopen MCA 105
CategoryDC Drives
LanguageEnglish

Related product manuals