N O T I C E
This option is only available in FC 302.
Parameter 15-13 Logging Mode
Table 772: Parameter 15-13 Logging Mode
Default value: [0] Log always
Change during operation: True
Select [0] Log always for continuous logging.
Select [1] Log once on trigger to start and stop logging conditionally using parameter 15-12 Trig-
ger Event and parameter 15-14 Samples Before Trigger.
Parameter 15-14 Samples Before Trigger
Table 773: Parameter 15-14 Samples Before Trigger
15-14 Samples Before Trigger
Parameter type: Range, 0 - 100
Change during operation: True
Before a trigger event, enter the percentage of all samples which should be retained in the log. See also parameter 15-12 Trigger
Event and parameter 15-13 Logging Mode.