Parameter 0-77 DST/Summertime End
Table 49: Parameter 0-77 DST/Summertime End
Default value: Size related
Parameter type: Range, 0 - 0
Change during operation: True
Sets the date and time when DST/summer time ends. The date is programmed in the format selected in parameter 0-71 Date Format.
Parameter 0-79 Clock Fault
Table 50: Parameter 0-79 Clock Fault
Default value: [0] Disabled
Change during operation: True
Enables or disables the clock warning when the clock has not been set, or has been reset due to a power-down and no back-up is
installed. If VLT® Analog I/O Option MCB 109 is installed, [1] Enabled is default.
Parameter 0-81 Working Days
Table 51: Parameter 0-81 Working Days
Default value: Depending on the selected array element
Parameter type: Option, Array [7]
Change during operation: True
Array with 7 elements [0]–[6] shown below the parameter number in the display. Press [OK] and step between elements with [▵]
and [â–¿]. Set for each weekday if it is a working day or a non-working day. The first element of the array is Monday. The working days
are used for timed actions.
Parameter 0-82 Additional Working Days
Table 52: Parameter 0-82 Additional Working Days
0-82 Additional Working Days
Default value: Size related
Parameter type: Range, 0 - 0, Array [5]
Change during operation: True
Array with 5 elements [0]–[4] shown below the parameter number in the display. Press [OK] and step between elements with [▵]
and [â–¿]. Defines dates for additional working days that would normally be non-working days according to parameter 0-81 Working
Days.