VLT
®
FCD Series
Installation
Diagram
* Integrated brake and mechanical brake control
and external 24 V are options.
RFI switches J1, J2
J1 and J2 must be removed at IT mains and
delta grounded mains with phase to earth voltage
> 300 V also during earth failure.
J1 and J2 can be removed to reduce leakage current.
Caution: No correct RFI filtering.
MG.04.B7.02 - VLT is a registered Danfoss trademark