Parameter Overview
*[0] Digital and ctrl.word
[1] Digital only
[2] Controlword only
8-02 Control Source
[0] None
*[1] FC Port
8-03 Control Timeout Time
0.1 - 6500.0s, * 1.0
8-04 Control Timeout Function
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
[20] N2 Override Release
8-06 Reset Control Word Timeout
*[0] No function
[1] Do reset
8-3* FC Port Settings
8-30 Protocol
*[0] FC
[2] Modbus RTU
[3] Metasys N2
[4] FLN
[5] BACNet
8-31 Address
1 - 247 , * 1
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001 - 0.500s, * 0.010
8-36 Max Response Delay
0.100 - 10.000s, *5.000
8-37 Max Inter-char delay
0.025 - 0.025s, * 0.025
8-5* Digital/Bus
8-50 Coasting Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-51 Quick Stop Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-52 DC Brake Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-53 Start Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-54 Reversing Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-55 Set-up Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-56 Preset Reference Select
[0] Digital input
[1] Bus
[2] Logic AND
*[3] Logic OR
8-7* Bacnet
8-70 BACnet Device Instance
0 - 0x400000UL
* 1
8-72 MS/TP Maxmaster
0 - 127, * 127
8-73 MS/TP Max Info Frames
1 - 65534, * 1
8-74 "I am" Service
*[0] Send at power-up
[1] Continuously
8-75 Intialisation Password
8-8* FC Port Diagnostics
8-80 Bus Message Count
0 - 65536, * 0
8-81 Bus Error Count
0 - 65536, * 0
8-82 Slave Message Rcvd
0 - 65536, * 0
8-83 Slave Error Count
0 - 65536, * 0
8-84 Slave Message Sent
0 - 65536, * 0
8-85 Slave Timeout Errors
0 - 65536, * 0
8-88 Reset FC port Diagnostics
*[0] Do not reset
[1] Reset counter
8-9* Bus Feedback
8-94 Bus feedback 1
-32768 - 32767, * 0
13-** Smart Logic
13-0* SLC Settings
13-00 SL Controller Mode
*[0] Off
[1] On
13-01 Start Event
[0] False
[1] True
[2] Running
[3] In range
[4] On reference
[7] Out of current range
[8] Below I
low
[9] Above I
high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input 18
[34] Digital input 19
[35] Digital input 27
[36] Digital input 29
*[39] Start command
[40] Drive stopped
[41] Reset trip
[42] Auto reset trip
[43] Key Ok
[44] Key Reset
[47] Key Up
[48] Key Down
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[83] Broken belt
13-02 Stop Event
See par. 13-02, *[40] Drive stopped
13-03 Reset SLC
*[0] Do not reset
[1] Reset SLC
13-1* Comparators
13-10 Comparator Operand
*[0] Disabled
[1] Reference
[2] Feedback
[3] Motor speed
[4] Motor current
[6] Motor power
[7] Motor voltage
[8] DC-link voltage
[12] Analog in 53
[13] Analog in 54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
[0] Less Than
*[1] Approx. Equal
[2] GreaterThan
13-12 Comparator Value
-9999.0 - 9999.0, * 0.0
13-2* Timers
13-20 SL Controller Timer
0.00 - 3600.00, * 0.00
13-4* Logic Rules
13-40 Logic Rule Boolean 1
See par. 13-01, *[0] False
13-41 Logic Rule Operator 1
*[0] Disabled
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND NOT
[8] NOT OR NOT
13-42 Logic Rule Boolean 2
See par. 13-01, *[0] False
13-43 Logic Rule Operator 2
See par. 13-41, *[0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-01, *[0] False
13-5* States
13-51 SL Controller Event
See par. 13-01, *[0] False
13-52 SL Controller Action
*[0] Disabled
[1] No action
[2] Select set-up 1
[3] Select set-up 2
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[25] Qstop
[26] DC Brake
[27] Coast
[28] Freeze output
Quick Guide VLT HVAC Basic Drive Quick Guide
MG18A302 - VLT
®
is a registered Danfoss trademark 31