8-32 Baud Rate
Option: Function:
The baud rate selection depends on the protocol selection in par.8-30
Protocol
.
[0] 2400 Baud
[1] 4800 Baud
[2] * 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol par.8-30
Protocol
using the Adjustable Frequency Drive Port.
For some of the protocols, not all options will be visible. Default depends on the protocol selected.
[0] * Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range: Function:
10. ms* [5. - 10000. ms] Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
8-36 Max Response Delay
Range: Function:
10001. ms* [11. - 10001. ms] Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word timeout.
8-37 Max Inter-Char Delay
Range: Function:
25.00 ms* [0.00 - 35.00 ms] Specify the maximum permissible time interval between receiving two bytes. This parameter acti-
vates timeout if transmission is interrupted.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-95