3.9 Main Menu - Communications and Options - Group 8
3.9.1 8-** Comm. and Options
Parameter group for configuring communications and options.
3.9.2 8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in par.8-50
Coasting Select
to par.8-56
Preset
Reference Select
.
[0] * Digital and ctrl. word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
8-02 Control Source
Option: Function:
Select the source of the control word: one of two serial interfaces or four installed options. During
initial power-up, the adjustable frequency drive automatically sets this parameter to
Option A
[3] if
it detects a valid serial communication bus option installed in slot A. If the option is removed, the
adjustable frequency drive detects a change in the configuration, sets par.8-02
Control Source
back
to default setting
Adjustable Frequency Drive Port
, and the adjustable frequency drive then trips. If
an option is installed after initial power-up, the setting of par.8-02
Control Source
will not change
but the adjustable frequency drive will trip and display: Alarm 67
Option Changed
.
[0] None
[1] FC RS-485
[2] FC USB
[3] * Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
NOTE!
This parameter cannot be adjusted while the motor is running.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-91
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals