8-55 Set-up Select
Option: Function:
Select control of the adjustable frequency drive set-up selection via the terminals (digital input) and/
or via the serial communication bus.
[0] Digital input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or serial communication option.
[2] Logic AND Activates the set-up selection via the serial communication bus/serial communication port, AND
additionally via one of the digital inputs.
[3] * Logic OR Activate the set-up selection via the serial communication bus/serial communication port OR via one
of the digital inputs.
NOTE!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option: Function:
Select control of the adjustable frequency drive Preset Reference selection via the terminals (digital
input) and/or via the serial communication bus.
[0] Digital input Activates Preset Reference selection via a digital input.
[1] Bus Activates Preset Reference selection via the serial communication port or serial communication op-
tion.
[2] Logic AND Activates Preset Reference selection via the serial communication bus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the serial communication bus/serial communication port
OR via one of the digital inputs.
NOTE!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
3.9.6 8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range: Function:
1 N/A* [0 - 4194304 N/A] Enter a unique ID number for the BACnet device.
NOTE!
This parameter is active only when par.8-30
Protocol
is set to [9]
Adjustable Frequency Drive Option
.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-98
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals