14-62 Inv. Overload Derate Current
Range: Function:
95 %* [50 - 100 %] Defines the desired current level (in % of rated output current for the adjustable frequency drive)
when running with reduced pump speed after load on the adjustable frequency drive has exceeded
the allowable limit (110% for 60 sec.).
3.15 Main Menu - Adjustable Frequency Drive Information - Group 15
3.15.1 15-** Drive Information
Parameter group containing adjustable frequency drive information such as operating data, hardware configuration and software versions.
3.15.2 15-0* Operating Data
Parameter group containing operating data, such as operating hours, kWh counters, power-ups, etc.
15-00 Operating Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the adjustable frequency drive has run. The value is saved when the adjust-
able frequency drive is turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the motor has run. Reset the counter in par.15-07
Reset Running Hours
Counter
. The value is saved when the adjustable frequency drive is turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647 kWh] Registering the power consumption of the motor as a mean value over one hour. Reset the counter
in par.15-06
Reset kWh Counter
.
15-03 Power-ups
Range: Function:
0 N/A* [0 - 2147483647 N/A] View the number of times the adjustable frequency drive has been powered up.
15-04 Over Temps
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of adjustable frequency drive temperature faults which have occurred.
15-05 Over Volts
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of adjustable frequency drive overvoltages which have occurred.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-143
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage