2-17 Over-voltage Control
Option: Function:
Overvoltage control (OVC) reduces the risk of the adjustable frequency drive tripping due to over-
voltage on the DC link caused by generative power from the load.
[0] Disabled No OVC required.
[2] * Enabled Activates OVC.
NOTE!
The ramp time is automatically adjusted to avoid tripping of the adjustable frequency drive.
3.5 Main Menu - Reference/Ramps - Group 3
3.5.1 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
Please also see par. 20-0* for information on settings in closed-loop.
3-02 Minimum Reference
Range: Function:
0.000 Ref-
erenceFeed-
backUnit*
[-999999.999 - par. 3-03 Referen-
ceFeedbackUnit]
Enter the Minimum Reference. The minimum reference is the lowest value obtainable by summing
all references. The minimum reference value and unit matches the configuration choice made in
par.1-00
Configuration Mode
and par.20-12
Reference/Feedback Unit
, respectively.
NOTE!
This parameter is used in open-loop only.
3-03 Maximum Reference
Range: Function:
50.000 Ref-
erenceFeed-
backUnit*
[par. 3-02 - 999999.999 Referen-
ceFeedbackUnit]
Enter the maximum acceptable value for the remote reference. The Maximum Reference value and
unit matches the configuration choice made in par.1-00
Configuration Mode
and par.20-12
Refer-
ence/Feedback Unit
, respectively.
NOTE!
If operating with par. 1-00, Configuration Mode set for Closed-loop [3], par.
20-14, Maximum Reference/Feedb. must be used.
3-04 Reference Function
Option: Function:
[0] * Sum Sums both external and preset reference sources.
[1] External/Preset Use either the preset or the external reference source.
Shift between external and preset via a command on a digital input.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-33
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals