15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset Select
Do not reset
[0] if no reset of the kWh counter is desired.
[1] Reset counter Select
Reset
[1] and press [OK] to reset the kWh counter to zero (see par.15-02
kWh Counter
).
NOTE!
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset Select
Do not reset
[0] if no reset of the Running Hours counter is desired.
[1] Reset counter Select
Reset counter
[1] and press [OK] to reset the Running Hours counter (par.15-01
Running
Hours
) and par.15-08
Number of Starts
to zero (see also par.15-01
Running Hours
).
15-08 Number of Starts
Range: Function:
0 N/A* [0 - 2147483647 N/A] This is a readout parameter only. The counter shows the numbers of starts and stops caused by a
normal Start/Stop command and/or when entering/leaving sleep mode.
NOTE!
This parameter will be reset when resetting par.15-07
Reset Running Hours Counter
.
3.15.3 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data sources (par.15-10
Logging Source
) at individual rates (par.15-11
Logging Interval
). A trigger
event (par.15-12
Trigger Event
) and window (par.15-14
Samples Before Trigger
) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be logged.
[0] * None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-144
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals