15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset Select
Do not reset
[0] if no reset of the kWh counter is desired.
[1] Reset counter Select
Reset
[1] and press [OK] to reset the kWh counter to zero (see par.15-02
kWh Counter
).
NOTE!
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset Select
Do not reset
[0] if no reset of the Running Hours counter is desired.
[1] Reset counter Select
Reset counter
[1] and press [OK] to reset the Running Hours counter (par.15-01
Running
Hours
) and par.15-08
Number of Starts
to zero (see also par.15-01
Running Hours
).
15-08 Number of Starts
Range: Function:
0 N/A* [0 - 2147483647 N/A] This is a readout parameter only. The counter shows the numbers of starts and stops caused by a
normal Start/Stop command and/or when entering/leaving sleep mode.
NOTE!
This parameter will be reset when resetting par.15-07
Reset Running Hours Counter
.
3.15.3 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data sources (par.15-10
Logging Source
) at individual rates (par.15-11
Logging Interval
). A trigger
event (par.15-12
Trigger Event
) and window (par.15-14
Samples Before Trigger
) are used to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be logged.
[0] * None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
3 Parameter Description VLT
®
HVAC Drive Programming Guide