8-72 MS/TP Max Masters
Range: Function:
127 N/A* [0 - 127 N/A] Define the address of the master which holds the highest address in this network. Decreasing this
value optimizes polling for the token.
NOTE!
This parameter is active only when par.8-30
Protocol
is set to [9]
Adjustable Frequency Drive Option
.
8-73 MS/TP Max Info Frames
Range: Function:
1 N/A* [1 - 65534 N/A] Define how many info/data frames the device is allowed to send while holding the token.
NOTE!
This parameter is active only when par.8-30
Protocol
is set to [9]
Adjustable Frequency Drive Option
.
8-74 "Startup I am"
Option: Function:
[0] * Send at power-up
[1] Continuously Choose whether the device should send the "I-Am" service message only at power-up or continu-
ously with an interval of approx. 1 min.
NOTE!
This parameter is active only when par.8-30
Protocol
is set to [9]
Adjustable Frequency Drive Option
.
8-75 Initialization Password
Range: Function:
0 N/A* [0 - 0 N/A] Enter the password needed for execution of Drive Re-initialization from BACnet.
NOTE!
This parameter is active only when par.8-30
Protocol
is set to [9]
Adjustable Frequency Drive Option
.
3.9.7 8-8* Adjustable Frequency Drive Port Diagnostics
These parameters are used for monitoring the bus communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid messages detected on the bus.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-99
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage