23-51 Period Start
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the energy log starts update of the counters. First data will be stored
in counter [00] and start at the time/date programmed in this parameter.
Date format will depend on setting in par.0-71
Date Format
and time format on setting in par.
0-72
Time Format
.
NOTE!
When mounting an Analog I/O MCB109 option card, a battery back-up of the date and time is included.
23-53 Energy Log
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with a number of elements equal to the number of counters ([00]-[xx] below parameter
number in display). Press OK and Step between elements by means of
and
buttons on the
Local Control Panel.
Array elements:
Data from latest period is stored in the counter with the highest index.
At power-down, all counter values are stored and resumed at next power-up.
NOTE!
All counters are automatically reset when changing the setting in par.23-50
Energy Log Resolution
. At overflow the update of the
counters will stop at maximum value.