5 Parameter Lists
5.1 Parameter Options
5.1.1 Default settings
Changes during operation:
“TRUE” means that the parameter can be changed while the adjustable frequency drive is in operation, and “FALSE” means that the adjustable frequency
drive must be stopped before a change can be made.
4 set-up:
'All set-up': the parameter can be set individually in each of the four set-ups, i. e., one single parameter can have four different data values.
’1 set-up’: data value will be the same in all set-ups.
SR:
Size related
N/A:
No default value available.
Conversion index:
This number refers to a conversion figure used when writing or reading by means of an adjustable frequency drive.
Conv. index 100 67 6 5 4 3 2 1 0 -1 -2 -3 -4 -5 -6
Conv. factor 1 1/60 1000000 100000 10000 1000 100 10 1 0.1 0.01 0.001 0.0001 0.00001 0.000001
Data type Description Type
2 Integer 8 Int8
3 Integer 16 Int16
4 Integer 32 Int32
5 Unsigned 8 Uint8
6 Unsigned 16 Uint16
7 Unsigned 32 Uint32
9 Visible String VisStr
33 Normalized value 2 bytes N2
35 Bit sequence of 16 Boolean variables V2
54 Time difference w/o date TimD
VLT
®
HVAC Drive Programming Guide 5 Parameter Lists
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
5-1