Seepage Tolerance
Seepage Tolerance in litres vs. jumper setting row D and meter size.
Meter
Qn
Imp/l D1 D2 D3 D4 D5 D6 D7 D8
1,6 100 0.01 0.02 0.05 0.1 0.2 0.5 1 2
2,5 60 0.017 0.033 0.083 0.167 0.333 0.833 1.67 3.33
4 50 0.02 0.04 0.1 0.2 0.4 1 2 4
6,3 25 0.04 0.08 0.2 0.4 0.8 2 4 8
10 15 0.067 0.133 0.333 0.667 1.333 3.33 6.67 13.3
16 10 0.1 0.2 0.5 1 2 5 10 20
25 6 0.167 0.333 0.833 1.67 3.33 8.33 16.7 33.3
40 5 0.2 0.4 1 2 4 10 20 40
Function Select for digital inputs
Jumper
Mode
F3 F2 F1
(ABA)
DIP1
(AIA)
DIP2
Comment
0
out out out
INH HDY Compatibility mode
1
out out in
INH+VFO HDY+VEN
2
out in out
INH+VFO HDY+VCL
3
out in in
INH+VFO HDY
4
in out out
INH HIP
5
in out in
INH+VFO HIP
6
in in out
INH HIP+VFO
7
in in in
INH+VFO HIP+VFO
Abbreviations:
INH: Inhibit (suppress) – activation resets all leak monitors, which are subsequently disabled while
the input remains activated.
VFO: Valve Force Open – activation forces cut-off valve to open position.
HDY: Holiday – activation selects Low Phase.
VEN: Valve Enable – activation releases valve for closure (otherwise forced open).
VCL: Valve Close – activation closes valve. ABA signal at DIP1 may force valve open.
HIP: High Phase – activation selects High Phase.
Note! When PIR sensors govern consumption phase, input DIP2 as well as key ’Holiday’ are disabled!
In modes 6 and 7, the valve is forced open when PIR sensors have set High Phase (Presence (of
persons)).
Note! A delay of several seconds may occur from a jumper is moved until the new function activates.