Hygrostat and other control options
Hygrostat
The control is prepared for connection of a hygrostat which is placed in the room to be
dehumidified or in the supply air duct – (air inlet).
Hygrostat is available as accessory.
Connection of
hygrostat
Please follow this procedure to connect a hygrostat.
The outlet for the hygrostat is 12 V.
Step Action
1 The hygrostat is connected to the terminals 3 and 4 after having taken away
the bridge
Room thermostat
The control is prepared for connection of a room thermostat which is placed in the room
to be dehumidified or in the supply air duct – (air inlet).
Room thermostat is available as accessory.
Connection of
room thermostat
Please follow this procedure to connect a room thermostat.
The outlet for the room thermostat is 12 V.
Step Action
1 The thermostat is connected to the terminals 5 and 6 after having taken
away the bridge
Continued overleaf