10
Technical data DFC 350
Introduction
This Free Cooling unit is very compact, quiet and economic due to the Displacement
Free Cooling system. In this product the EC-fan signal is reduced to 5V to get the opti-
mized performance.
Air flow and sound
This table shows the technical data for airflow and sound pressure:
Parameter
48V DC
230V AC
Max air flow
514 m
3
/h
514 m
3
/h
Max air flow
143 l/s
143 l/s
Free cooling capacity at Δt=5°C
3 kW
3 kW
Max power consumption
40 W
35 W
Sound pressure at 5m from shelter
36 dB(A)
34 dB(A)
Sound pressure at 10m from shelter
31 dB(A)
31 dB(A)
Cabinet
This table shows the specifications for the cabinet:
Specification
Designation
DFC 350
Weight
Controller included
10 kg
Metal sheet material
Aluzinc AZ150
0,8-1,5 mm
Fan motor
This table shows the data for the fan motor:
Voltage version
48V DC
230V AC
Voltage nominal
48V DC
230V AC
Current
2,3 A
0,9 A
Max power consumption at standard settings
40 Watt
35 Watt
Speed
1500 rpm
1500 rpm
Filter
This table shows the data for the filter:
Specification
Filter data
Type
Bag filter
Filter Class
F6
Total Area
1,4 m
2
Recommended filter monitor settings
150 Pa