The DL250 has the ability to report a low battery code to the base station when AC power has been lost and the battery has
discharged down to 10.3 Volts. Low battery will also report if the dynamic battery test fails. The desired communicator code
must be programmed into these locations. When contact I.D is selected, program a "1" in Data 1 to report event "302 -Low
Battery" or “309- Fail Dynamic Battery Test”. When using Ademco High Speed, program a one (1) in Data 1 to enable this
report, a "5155 5555 6" Low Battery and Fail Dynamic Battery Test. Note: A restore code will not be report for a “Dynamic
Battery Fail” event, however, the “Dynamic Battery Fail” event code will be reported on every Dynamic Battery Test time
until the battery problem is corrected. If Data 1 is "0", Low Battery is disabled. The defaults are “1:0:0:5" with telephone
number 1 and the event log enabled.
SINGLE LOCATION COMMUNICATOR CODES
The following communicator code are programmed in one location only. When Contact I.D. or Ademco High Speed is
selected then programming a “1" in the selected location will enable the communicator event report and a “0" will disable
the communicator event report.
LOCATION 328: AC POWER RESTORE COMMUNICATOR CODE
The 250 has the ability to report to the base station when the AC power has been restored. Once the AC power has been
restored to the 250, there will be a delay time before the restore code will be sent to the base station. The time programmed
into location 330 for AC loss delay will also be the restore delay. Program a "1" into this location to enable AC power loss
restore reports. Program a "0" into this location to disable restore reports. Default for AC power restore code is “1" enabled.
LOCATION 329: LOW BATTERY RESTORE COMMUNICATOR CODE
The 250 has the ability to send a restore code to the base station when the battery voltage is restored to normal operating
level (above 10.3 volts). Program a "1" into this location to enable low battery restore codes. Program a "0' into this location
to disable low battery restore codes. Default for low battery restore code is “1" enabled.
LOCATION 331: RESERVED
LOCATION 330: AC POWER FAIL REPORT DELAY
The number programmed into location 330 represents the number of 1 minute increments the AC power is lost before a
communication is initiated, from 1 to 15 minutes. Factory default is "5" which will delay AC power loss for 5 minutes. The
AC power restore if enabled in location 328, and will also delay reporting until after the number of minutes programmed in
this location has elapsed. If a "0" is selected (instant) the delay will be approximately 20 seconds. This is to allow for
transients and power surges.
LOCATION 332: RESTORE CODE FOR Zones 1-8
Location 332 is used to program the Restore code for zones (1 thru 16), when Contact I.D and Ademco High Speed is
selected. Note: Zone Restore codes can only be reported if Zones are enabled to report Restores in the “Zone Report /
Special Characteristics” locations per individual zone. Default for Zone restore code is “1" enabled.
LOCATION 333: RESTORE CODE FOR Zones 9-16
These locations should remain at factory default when Contact I.D and Ademco High Speed are selected.
LOCATION 334: ISOLATE CODE FOR Zones 1-8
Location 334 is used to program reporting of the Isolate code for zones (1 thru 16), when Contact I.D and Ademco High
Speed is selected. Note: Zone Isolate codes can only be reported if Zones are enabled to report Isolates in the “Zone Report
/ Special Characteristics” locations per individual zone. When contact I.D is selected, program a one (1) in this location to
enable this report, an event "570 - Zone Isolate" will be reported. When using Ademco High Speed, program a one (1) in
this location to enable this report. A one (1) will be displayed for the channel corresponding to the zone that is Isolated. EG,
"5155 5555 3" will be reported for zone two (2). Default for Zone Isolate code is “1" enabled.
LOCATION 335: ISOLATE CODE FOR Zones 9-16