21
Hot Gas Lines
Table 2 Hot Gas Lines (Inches OD) (Single Circuit Systems)
Unit
Tonnage
Tons
per
Circuit
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
6
6
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
8
8
7/8
7/8
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
10
10
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
1-3/8
7/8
13
13
1-1/8
1-1/8
1-1/8
1-1/8
1-3/8
1-1/8
1-3/8
1-1/8
Table 3 Hot Gas Lines (Inches OD) (Dual Circuit Systems)
Unit
Tonnage
Tons
per
Circuit
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
Horizontal &
Vertical Down
Vertical
Up
6
3
5/8
5/8
5/8
5/8
7/8
5/8
7/8
5/8
8
4
7/8
5/8
7/8
5/8
7/8
5/8
7/8
5/8
10
5
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
13
6.5
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
Liquid Lines
Table 4 Liquid Lines (Inches OD) (Single Circuit Systems)
Unit
Tonnage
Tons per
Circuit
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
6
6
5/8
5/8
5/8
5/8
8
8
7/8
7/8
7/8
7/8
10
10
7/8
7/8
7/8
7/8
13
13
7/8
7/8
7/8
7/8
Table 5 Liquid Lines (Inches OD) (Dual Circuit Systems)
Unit
Tonnage
Tons per
Circuit
Equivalent Feet (Meters)
50 (15.2)
100 (30.5)
150 (45.7)
200 (61.0)
6
3
1/2
1/2
5/8
5/8
8
4
1/2
5/8
5/8
5/8
10
5
1/2
5/8
5/8
5/8
13
6.5
5/8
5/8
5/8
5/8

Table of Contents