EasyManua.ls Logo

Data Aire DAL-06 - Additional Oil; Table 20 Refrigerant Charge Values

Data Aire DAL-06
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
glass are not unusual at this point. It is likely that more refrigerant will be required to complete the
charging procedure.
Finish charging circuit 1 by slowly opening the valve on the refrigerant manifold set to meter liquid
refrigerant into the low side of the system. Use a liquid charging adapter to prevent liquid refrigerant
from entering the compressor.
NOTICE: Charging to a full liquid line sight glass should never be the sole
means of determining the correct refrigerant charge. Other parameters such
as superheat, suction pressure, head pressure, subcooling and ambient
temperature are also important factors. A system charged to a clear sight
glass is often overcharged.
Adjust the refrigerant charge to the subcooling value shown in the table below and the sight glass has
sparse bubbles. The unit should be allowed to stabilize for 15 to 20 minutes to verify key measurements
in Table 20 Refrigerant Charge Values below.
Table 20 Refrigerant Charge Values
Function
R-410A Conditions
R-407C Conditions
Discharge Pressure
322 PSIG (2220 kPa)
minimum
199 PSIG (1372 kPa)
minimum
Liquid Line Pressure
290 to 390 PSIG
(2000 to 2688 kPa)
245 to 285 PSIG
(1689 to 1965 kPa)
Liquid Line
Temperature
85 to 100°F
(29.4 to 37.8°C)
106 to 115°F
(41.1 to 46.1°C)
Suction Pressure
103 to 130 PSIG
(710 to 896 kPa)
53 to 70 PSIG
(365 to 483 kPa)
Suction Saturated
Temperature
33 to 45°F
(0.56 to 7.2°C)
33 to 45°F
(0.56 to 7.2°C)
Subcooling
8 to 15°F
(-13.3 to -9.4°C)
8 to 10°F
(-13.3 to -12.2°C)
Differential Temperature - Depending on ambient conditions, at
compressor’s maximum speed
Superheat
8 to 18°F
(-13.3 to -7.8°C)
8 to 15°F
(-13.3 to -9.4°C)
Differential Temperature
Measure the superheat at the compressor suction line at least 6 inches (152 mm) away from the
compressor. Measure subcooling at the liquid line.
Additional Oil
When charging is complete, add the correct amount of oil to each circuit. In installations with good oil
return and line runs up to 50 ft (15 m), no additional oil is required. If installation lines exceed 50 ft (15
m), additional oil needs to be added. 1 or 2% of the total system refrigerant charge (in weight) can be
used to roughly define the required oil top-up quantity.

Table of Contents

Related product manuals