6.0 GLYCOL SYSTEMS
6.1 Glycol Concentration
The system must be lled with water and the appropriate amount of ethylene or propylene glycol
to protect against winter freezing. To achieve the approximate glycol concentration, it is necessary
to know the total system volume. The total system volume consists of the uid cooler volume, the
evaporator unit volume and the volume of the inter-connecting piping.
The following tables can be used for arriving at an approximate system volume. After installation,
the glycol percentage should be checked. The glycol percentage should be checked at regular in-
tervals to ensure against freeze protection.
6.2 Internal (Fluid) Volume
Evaporator Model
Volume (gallons)
no Energy Saver Coil
Volume (gallons)
with Energy Saver Coil
DAMG 01 0.5 2.0
DAMG 1.5 0.5 2.0
DAMG 02 0.5 2.5
DAMG 2.5 0.5 2.5
6.3 Fluid Cooler Internal Volume
Fluid Cooler Volume (gallons) Fluid Cooler Volume (gallons)
DAFC 06 2.5 DAFC 17 6.6
DAFC 07 3.4 DAFC 21 7.4
DAFC 09 4.2 DAFC 24 9.8
DAFC 11 3.3 DAFC 29 12.3
DAFC 15 4.9
6.4 Copper Piping Internal Volume
Pipe Diameter Inches
O.D.
Volume per 100 feet of pipe (gallons)
5/8 1.2
3/4 1.8
7/8 2.5
1-1/8 2.5
1-5/8 4.3
2-1/8 9.2