Temperature Assist – If set to “Yes”, Unit 1 will be allowed to request additional standby
units to come on when the average zone temperature is higher than the cooling set point
plus dead band plus 1.5°F*.
ES Before DX: If set to “Yes”, (default is No) all units in the zone will run in CW Energy
Saver mode prior switching to DX cooling. Use this feature only when all units in the zone
have CW cooling and are set to Energy Saver mode.
Tmp Assist Band: (only shown when ES Before DX is enabled). Offers an adjustable
band of 1.0 to 10.0 degrees (default of 1.5) instead of the fixed 1.5°F for temperature
assist.
Engy DX Band: (only shown when ES Before DX is enabled). Offers an adjustable band
of 1.3 to 10.0 degrees (default of 1.3) instead of the fixed 1.3°F threshold that is added to
DX staging when energy saver is running.
Standby On Delay – This is how long Unit 1 will wait before requesting a standby unit to
turn on. The range of time is 30 to 999 seconds, with a default setting of 30 seconds.
Standby Off Delay – This is how long Unit 1 will wait before allowing a unit to return to
standby. The range of time is 30 to 999 seconds, with a default of 900 seconds. Note:
although Unit 1 may allow a unit to return to standby after this delay period, the unit may
continue to run if the “Finish Run->Stby” selection is set to Yes.
Enable Inhibit – If set to Yes (default and recommended setting), the Zone Control will
prevent units from performing conflicting operations. For example: If any unit is cooling,
others will be prevented from heating. If any unit is dehumidifying, then other will be
prevented from humidification.