MENU B SETPOINTS continued
dehumidification will begin. The range of adjustment is 50.0 to 65.0 °F with a
default value of 59.0 °F.
High Dewpoint Db: This is the High Dewpoint Deadband. It is the amount that the
dewpoint must drop below setpoint before dehumidification ends. The range of
adjustment is 1.0 to 3.0 °F with a default value of 1.0 °F.