S
e
t
-
B
ac
k
S
e
tt
i
n
g
s
C
oo
li
n
g
S
e
t
po
i
n
t:
77
.
0
•
H
ea
t
i
n
g
S
e
t
po
i
n
t:
67
.
0
•
H
u
m
i
d
i
f
y
O
ffs
e
t:
55
%
D
e
hu
m
i
d
i
f
y
O
ffs
e
t:
45
%
Note on gPOD models: In addition to the clock/time schedular, Night Time
setpoints are also used when an optional light sensor detects an absence of light
(input is turned on).
Cooling Setpoint: Temperature set point for cooling, used when the scheduler is
in set-back mode. The range of adjustment depends the temperature being
controlled:
Return air: range is 65 to 85°F with a default value of 77°F.
Discharge air: range is 45 to 85°F with a default value of 77°F.
(If model is IRDX or CW only (no DX), maximum range increases to 105°F)
Heating Setpoint: Temperature set point for heating, used when the scheduler is
in set-back mode. The range of adjustment depends the temperature being
controlled:
Return air: range is 65 to 85°F with a default value of 67°F.
Discharge air: range is 45 to 85°F with a default value of 67°F.
(If model is IRDX or CW only (no DX), maximum range increases to 105°F)
Humidify Setpoint: The humidifier setpoint, used when the scheduler is in set-
back mode. The range of adjustment is 25 to 70% with a default value of 45%.
Dehumidify Setpoint: The dehumidification setpoint, used when the scheduler is
in set-back mode. The range of adjustment is 25 to 70% with a default value of
55%.