71
MENU K ALARMS & LIMITS (Service Level) continued
P
u
m
p
-
D
o
w
n
A
l
a
r
m
F
a
il
e
d
PD
A
l
a
r
m
:
Y
e
s
N
o
t
e
:
P
u
m
p
-
D
o
w
n
f
ea
t
u
r
e
w
ill
s
t
ill
op
e
r
a
t
e
.
The Pump-Down Alarm screen will only appear if the feature is enabled in the
Factory menu.
Failed PD alarm: When set to Yes” (default) the pump-down alarm is enabled. If
set to No, the pump-down cycle will still operate, but without an alarm. The PD
alarm results from a PD cycle taking too long or if there are more than three PD
cycles required.
P
h
a
s
e
L
o
ss
A
l
a
r
m
A
c
t
i
on
:
No
A
l
a
r
m
This Phase Loss Alarm screen is only shown when the optional power meter is
installed and configured in the factory menu.
Action: The action to a phase loss alarm setting has three choices:
No Alarm: (Default setting). The phase alarm is disabled.
Alarm Only: The phase alarm is enabled but has no further action.
Alm & Turn Off: The phase alarm is enabled and will cause the unit to turn
off in the event of the alarm.