MENU K ALARMS & LIMITS (Service Level) - Custom Inputs
A
l
a
r
m
I
npu
t
s
C
u
s
t
o
m
A
l
a
r
m
M
e
ss
age
s
A
l
a
r
m
#1
(
D
I-
13
)
SEE
TAG
I
N
S
I
D
E
DOO
R
A
l
a
r
m
#2
(
D
I-
14
)
SEE
TAG
I
N
S
I
D
E
DOO
R
Each of the custom alarm inputs can be given a unique message that will appear
on its alarm screen. Some messages also carry out a function as noted below.
Additional sensors or switches may also be required. The selections are:
SEE TAG INSIDE DOOR (default setting)
REHEAT INHIBITED The reheat function is disabled.
HUMIDIFIER INHIBITED The humidifier function is disabled.
REHEAT & HUM INHIBITED The reheat and humidifier functions are disabled.
UNIT IN STBY Not an alarm. Unit status screen will indicate STANDBY”.
UPS ON-CHK MAIN PWR
STANDBY PUMP ON
CHK HUMIDIFIER CYL
FAN MOTOR OVERLOAD - Inhibits heat and humidifier functions.
AE DAMPER NOT OPEN See Airside Economizer Operation
AE DAMPER NOT CLOSED See Airside Economizer Operation
POWER A OPERATING Message only, does not cause an alarm
POWER B OPERATING Message only, does not cause an alarm
POWER A NOT AVAILABLE
POWER B NOT AVAILABLE
COMPRESSOR VFD ALARM
HUM FLT-CHK WTR PR
C1 HIGH PRESSURE
C2 HIGH PRESSURE
C1 LOW PRESSURE
DIRTY FILTER
SMOKE DETECTOR Alarm turns the unit off and remains active when unit is off.
NO FLOW-CHECK PUMP
*Note: Some selections require optional equipment.