10•dara-4g
2
User Manual
•MenusandSettings
MENU SETTINGS
A - On/Off Start-Delay : 5s (5s-600s)
Start-up Mode: Off (On)
C - Clock Day
Date
Hour
D - Input/Output
No programming or settings. Only to view panel inputs and outputs
D=digital and B= binary
E - Historical Data
->Scroll Up/Down? Press Enter then use Up/down button to view alarm
history and unit runtimes
F - ?Information Data Aire Inc.
Model dara-4g2
Ver : 0.1
Controller ID: 001
BIOS 6.09 11/12/12
Boot: 4:07 12/18/09
G-NetworkCong BMS PORT 1
Protocol: N/A – Modbus RTU, BACnet MSTP and BACnet TCP/IP*
*Optional network card required.
H - Calibrate Sensor Zone Temperature (Optional Zone sensor required)
Input B001
Offset: 0.00
Value 72.01 (current value)
Zone humidity (Optional Zone sensor required)
Input B002
Offset: 0.00
Value: 48.00 (current value)
I - Manual Control
Return to Auto: 10s (10-300s) Time delay to reverse manual mode to auto
mode- This is used for relays testing only.
Unit 1 Auto Off/On (change to Man then toggle off to on or on to off)
Unit 2 Auto Off/On
Unit 3 Auto Off/On
Unit 4 Auto Off /On
Alarm Auto Off /On
Manual Override
Manual DI 1: OFF
Manual Position: CLOSED
DI 1 Status: Open (Turn on a manual override switch to test input)
J - Factory Settings Screen Flip Delay: 2s (2-10s)
Units in the Zone: 2 (1-4)
Number Units On: 1 (1-4)
Temp. Sensor: Not Used (Installed)