11•dara-4g
2
User Manual
Humidity Sns: Not Used (Installed)
Change Over Delay: 5s (5-600 seconds)
Time Rotation: 24 hrs (4 hrs,8 hrs,12 hrs,24 hrs,7 days,14 days,30 days)
Current lead: Unit1
Days: 00 Hrs: xx Mins:xx
Force Rotation: No/Yes
Temp Units: Fahrenheit
Zone High Temp: 72 (65-85)
Deadband: 2 (1-5)
Temperature Assist: Yes/No
Min Assist Time: 15M (15-60M)
Language: English
Clear User settings and replace them with factory defaults? No
(Change from No to Yes will put all settings back to default value)
K - Alarms & Limits Audio Mode: Short beep (Long beep, Full beep, None)
UnitAction:Condition(Turnoff,Stayon)deneschange-overlogicon
alarm condition- See alarm logic for details.
Reset Alarm Log: No/Yes
Alarm Screen Contact: No Contact message, Data Proc. Mngr, Custom
message, Service Company, Maint. Engineer (select one)
L-CongI/O Factory used only