AIR-COOLED FLUID COOLER
34 Air-Cooled Condenser Manual
7.8 Maintenance Functions
Monthly
Inspect fluid cooler for obstruction to the inlet air side of the coil
Inspect the motor/fan blade assemblies to ensure the bearings
are free and the motor mounts and fan(s) are secure
Bleed air from the system
Seasonally
Inspect electrical components for loose wire connections
Inspect contactor contacts for pitting Check glycol solution level in the
system Inspect fan motor(s)
In the winter, do not allow snow to accumulate or build-up around
the sides or underneath the coil
Bi-Annually
Check the glycol solution inhibitors. Flush as necessary
Clean the fluid cooler coil of all debris that could restrict airflow
Annually
Check the glycol system for leaks and corrosion