Installation, Operation and Maintenance Manual
Page v
and free of obstructions and in good condition with no visible sign of damage or
leaks. Improper installation, application and service practices can result in water
leakage from the unit. Water leakage can result in severe property damage and
loss of critical data center equipment. Do not locate unit directly above any
equipment that could sustain water damage. Data Aire recommends installing
leak detection equipment for unit and supply lines.
NOTICE Risk of a leaking coil due to freezing and/or corrosion can cause
equipment and serious building damage. Cooling and heat rejection coils, heat
exchangers and piping systems that are connected to open cooling towers or
other open water/glycol systems are at high risk for freezing and premature
corrosion. Fluids in these systems must contain the proper antifreeze and
inhibitors to prevent freezing and premature coil corrosion. The water or
water/glycol solution must be analyzed by a competent water treatment
specialist before startup to establish the inhibitor requirement. The water or
water/glycol solution must be analyzed every six months to determine the
pattern of inhibitor depletion. The complexity of water-caused problems and
their correction makes it important to obtain the advice of a water treatment
specialist and follow a regularly scheduled maintenance program.
NOTICE Installation and maintenance must be performed only by qualified
personnel who are familiar with this type of equipment.
WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used
and recovered responsibly. Failure to follow this warning may result in personal
injury or death.
CAUTION Do not operate doors when unit is not on a flat surface.
WARNING Pressure-relief line must be vented to the atmosphere per the latest
edition of ASHRAE standard and/or any local building, fire or mechanical codes.
This is for units with shell and tube and units with high pressure relief valve.
NOTICE Maintain a minimum clearance of 36 inches or width of the unit
whichever is larger.
NOTICE Altering, modification or equal of our product may void warranty and
or void regulatory certification(s). Field rearrangement of components are not
recommended.