Program Group: Engine Parameters (continued)
Set
Crank Timer sec 10
This is the maximum start period. Starting will be
automatically cancelled if the genset fires before the
timer.
Wait Between Starts sec 10 This is the waiting period between two start attempts.
Engine Heating Timer sec 4
This is the period used for engine heating following
the program parameter.
Cooldown Timer min 1.0
This is the period that the generator runs for cooling
purpose after the load is transferred to mains.
Stop Solenoid Timer sec 10
This is the maximum time duration for the engine to
stop. During this period the STOP relay output is
energized (if assigned by Relay Definitions). If the
genset has not stopped after this period, a FAIL TO
STOP warning occurs.
Number of Starts - 3 This is the maximum number of start attempts.
Engine Heating Method - 0
This parameter defines the engine heating method.
The genset will not take the load before engine
heating is completed.
0: engine is heated during Engine Heating Timer.
1: engine is heated until the coolant temperature
reaches the Engine Heating Temperature and at
least during the Engine Heating Timer.
Service Engine Hours hour 50
The
led indicator will turn on
after this quantity of engine hours from the last
service. If the period is set to ‘0’ no SERVICE
REQUEST will be generated depending on engine
hours.
Service Period month
6
The
led indicator will turn on
after this amount of time from the last service. If the
period is set to ‘0’ no SERVICE REQUEST will be
indicated depending on time.
Idle Speed Timer sec 0
When the engine runs, the Idle output relay function
will be active during this timer.
Gas Solenoid Delay sec 5
The gas solenoid of the gas engine will be opened
after this delay during cranking.
Low Fuel Warning % 20
If the fuel level measured from the analog input falls
below this limit, a LOW FUEL LEVEL SENDER
warning is generated.
Low Fuel Shutdown % 10
the fuel level measured from the analog input falls
below this limit, a LOW FUEL LEVEL SENDER
shutdown alarm is generated and the engine stops.
Fuel Level sender Ohms ohms
180
Fuel level sender max resistance. 180 ohms and 300
ohms senders are common.