Program Group: Adjust Date and Time
Parameter
Definition
Unit
Factory
Set
Description
Date - 01-31 Current day of the month.
Month - 01-12 Current month.
Year - 00-99 Last two digits of the current year.
Hours - 00-23 Current hour of the day.
Minutes - 00-59 Current minute of the hour.
Seconds - 00-59 Current second of the minute.
Program Group: Weekly Schedule
Parameter
Definition
Unit
Factory
Set
Description
Monday Turn_on - 24:00
Please review chapter 9 for a detailed description of
weekly programming schedule operation.
Monday Turn_off - 24:00
Tuesday Turn_on - 24:00
Tuesday Turn_off - 24:00
Wednesday Turn_on - 24:00
Wednesday Turn_off - 24:00
Thursday Turn_on - 24:00
Thursday Turn_off - 24:00
Friday Turn_on - 24:00
Friday Turn_off - 24:00
Saturday Turn_on - 24:00
Saturday Turn_off - 24:00
Sunday Turn_on - 24:00
Sunday Turn_off - 24:00
Program Group: Sender Characteristics
Parameter
Definition
Unit
Factory
Set
Description
Oil Pressure Sender Ohms -
1
ohm
10 Oil Pressure Sender point 1, ohm value
Oil Pressure Value -1 bar
0.0 Oil Pressure Sender point 1, bar value
Oil Pressure Sender Ohms -
2
ohm
52 Oil Pressure Sender point 2, ohm value
Oil Pressure Value -2 bar
2.0 Oil Pressure Sender point 2, bar value
Oil Pressure Sender Ohms -
3
ohm
90 Oil Pressure Sender point 3, ohm value
Oil Pressure Value -3 bar
4.0 Oil Pressure Sender point 3, bar value
Oil Pressure Sender Ohms -
4
ohm
140 Oil Pressure Sender point 4, ohm value
Oil Pressure Value -4 bar
7.0 Oil Pressure Sender point 4, bar value
Oil Pressure Sender Ohms -
5
ohm
156 Oil Pressure Sender point 5, ohm value
Oil Pressure Value -5 bar
8.0 Oil Pressure Sender point 5, bar value
Oil Pressure Sender Ohms -
6
ohm
184 Oil Pressure Sender point 6, ohm value
Oil Pressure Value -6 bar
10.0 Oil Pressure Sender point 6, bar value