Program Group: Sender Characteristics (continued)
Parameter
Definition
Unit
Factory
Set
Description
Temperature Sender Ohms -
1
ohm
38 Temperature Sender point 1, ohm value
Temperature Value -1 °C
100 Temperature Sender point 1, °C value
Temperature Sender Ohms -
2
ohm
51 Temperature Sender point 2, ohm value
Temperature Value -2 °C
90 Temperature Sender point 2, °C value
Temperature Sender Ohms -
3
ohm
134 Temperature Sender point 3, ohm value
Temperature Value -3 °C
60 Temperature Sender point 3, °C value
Temperature Sender Ohms -
4
ohm
322 Temperature Sender point 4, ohm value
Temperature Value -4 °C
39 Temperature Sender point 4, °C value
Temperature Sender Ohms -
5
ohm
650 Temperature Sender point 5, ohm value
Temperature Value -5 °C
20 Temperature Sender point 5, °C value
Temperature Sender Ohms -
6
ohm
1630 Temperature Sender point 6, ohm value
Temperature Value -6 °C
02 Temperature Sender point 6, °C value