Timestamp
Index (dec) Parameter Object Name Length Subindex (o󰀨set) Value/Range Description Data Type Access* Remark
0x00B8 (184) Timestamp Trigger
1 octet
1 octet
1 octet
1 octet
1 octet
1(32)
2(24)
3(16)
4(8)
5(0)
0x00: disabled (default)
0x01: enabled
EVENT_1 (ID=0x01): Switch Counter Threshold Reached
EVENT_2 (ID=0x02): Temperature underrun (Event mode APPEARS)
EVENT_3 (ID=0x03): Temperature overrun (Event mode APPEARS)
EVENT_4 (ID=0x04): Short circuit
EVENT_5 (ID=0x05): Power fault
UIntegerT R/W
Event that generates a
timestamp
0x00B9 (185) Timestamp Features
1 octet
1 octet
1(8)
2(0)
3 [ms]
1 [ms]
Maximum timestamp latency time
Timestamp resolution
UIntegerT
UIntegerT
RO
RO
Latency between event
and timestamp (harware
dependent). Typically 3ms
0x00BA (186) Timestamp List 70 octets
*See format in
Timestamp table
ArrayT
OctetStringT
RO
Last timestamp trigger
starts counting from Power
Up or from Timestamp
Synch Value
0x00BB (187) Timestamp Synch Value
2 octets
1 octet
1 octet
1 octet
1 octet
1(32)
2(24)
3(16)
4(8)
5(0)
0...999
0...59
0...59
0...23
0...255
milliseconds
seconds
minuts
hours
days
UIntegerT R/W
Reset value for timestamp
synchronization command
0x00BC (188) Time Stamp New Event Flag 1 octet
0: false
1: true
Time Stamp New Event signaling Boolean RO
Index (dec) Command Name Length Value (dec) Description Access*
0x0002 (2) Reset Timestamp Application 1 octet 0xB1(177) Reset Timestamp application (Timestamp Trigger, Timestamp List and Timestamp New Event Flag) WO
0x0002 (2) Reset Timestamp 1 octet 0xB2(178) Reset clock counter WO
0x0002 (2) Timestamp Synchronization 1 octet 0xB3(179)
Start counting from the Timestamp Synch Value (index 187). This command clears the Timestamp List and resets the
Timestamp New Event Flag
WO
0x0002 (2)
Reset Timestamp New Event
Flag
1 octet 0xB4(180) Reset the Timestamp New Event Flag WO
TIMESTAMP TABLE
ID event day hours minutes seconds milliseconds
Last EVENT_X occured Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
Byte8 Byte9 Byte10 Byte11 Byte12 Byte13 Byte14
Byte15 Byte16 Byte17 Byte18 Byte19 Byte20 Byte21
... ... ... ... ... ... ...
... ... ... ... ... ... ...
... ... ... ... ... ... ...
First EVENT_X occured Byte64 Byte65 Byte66 Byte67 Byte68 Byte69 Byte70