Dectron, Inc. March 2012
Owner’s Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Stop Blowers T.A.B.
Data subject to change without notice.
205
DECTRON
If it is desired to stop the blower at this point, follow the steps below. If prompted for a password on units made
before 4/2005, enter 1793. For units made after 4/2005, enter 17 or 1793.
CAUTION: This method does not substitute for an approved lockout/tagout procedure.
GO TO
AUTO/OFF CONTROLS BLOWER Auto
COMPRESSOR #1 Off
COMPRESSOR #2 Off
TURNING BLOWER
OFF
ENTER TO CONFIRM
ESC TO CANCEL
Press
↑↑
or
↓↓
to toggle between
AUTOMATIC and OFF, then press
↵↵
to confirm.
Press
Esc repeatedly to return
to the main menu or default screen.
Press
↓↓
repeatedly to reach screen below.
MAIN MENU
SCROLL DOWN
FOR OPTIONS
Default Screen
HUMIDITY aaa / bbb %
ROOM AIR ccc / ddd F
Optional
Do not select compressor(s).
For a controller
interface map, see
Operation.
If possible and safe to do so, leave the electrical power connected to the unit and leave the blower
overload ON. This will allow the compressor crankcase heater(s) to function. The crankcase heaters must
be on continuously for at least 12 hours before the compressors are started.
Risk of contact with moving parts. Can cause injury or death.
This product contains rotating parts and V-belt drives. Some installation, service, and
maintenance procedures could expose personnel to the risk of injury or death from
contact with these parts.
Using only approved devices (e.g. locking safety switch), disconnect, lockout, and
tagout all sources of electrical energy before working inside the unit cabinet. Allow
adequate time for rotating parts to stop. Follow all applicable safety regulations.
The following method of stopping the blower does not
substitute for an
approved lockout/tagout procedure.
WARNING
T.A.B.
↵↵
↵↵
↵↵
↑↑
Esc
Esc
Esc
Esc