A remote condenser or DryCooler must be mounted level to within 1/4 bubble. Do not remove or shorten the
legs.
The feet must be secured to the mounting surface to prevent movement in high winds. Where seismic
mounting is used, care must be taken to prevent strains on the condenser or DryCooler or on connecting tubes
or conduits.
Where a remote condenser or DryCooler is mounted to a building surface, suitable pads (by others) should be
used to prevent the transmission of noise and/or vibration into the building.
Mounting Frame
(by others)
Suitable Fasteners
(by others)
at each foot
Anti-Vibration Pad
(by others) at
each foot
Condenser
or
DryCooler
Sample
Number of legs and
brackets may vary.
Other appearance
may vary.
Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owner’s Manual
Data subject to change without notice.
66
Lifting and Locating Remote Condenser Vibration Isolation
LIFTING AND
LOCATING