Dectron, Inc. March 2012
DECTRON
1. Check the calibration of the unit’s
compressor-discharge gas temperature
sensor by following the interface map
shown at right.
The indicated temperature should
agree with the reading of the installer’s
thermometer within 10°F (4°C). If it
does not, be sure your thermometer is
accurate, then contact Dectron if
necessary.
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owner’s Manual
Startup Check Discharge Sensor
Data subject to change without notice.
236
GO TO
SENSOR READINGS
INDOOR HUMIDITY
READING . . . xxx %
DISCHARGE X TEMP
READING . . . xxx %
MAIN MENU
SCROLL DOWN
FOR OPTIONS
Default Screen
HUMIDITY aaa / bbb %
ROOM AIR ccc / ddd F
Press
↓↓
repeatedly to reach screen below.
Press
↓↓
repeatedly to reach
the appropriate screen.
2. Replace the expansion-valve caps.
3. Return the set points to normal, as noted on the unit nameplate (see Product Description - Unit Nameplate).
4. IMPORTANT: Remove the temporary jumper wire across the CLP switch.
5. Close the access panels or doors.
6. If the unit has more than one refrigeration circuit and not all of the circuits have yet been adjusted, repeat pages
Prepare to Adjust Expansion Valve(s) through Check Discharge Sensor for other refrigeration circuits.
WARNING
Risk of blistering. May cause injury.
Some surfaces inside a unit may be at elevated temperatures. Use gloves and
other protective equipment to prevent injury.
NOTE: In the images and the discussion below, “aaa”, “bbb”, “ccc”, “ddd”, and “xxx” are placeholders.
Your screen will actually show the current values for your unit.