Dectron, Inc. March 2012
Owners Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Pool-Chemical Storage Facility Building Construction
Data subject to change without notice.
47
Chemical fumes will escape from containers and damage all metal equipment. The chemical storage space should
be well ventilated to the outdoors. Where an exhaust fan is used, a differential-pressure switch should cause an
alarm if the door is left open or if the fan fails.
Doors should not open from the chemical-storage space into a mechanical-equipment room or into the natatorium.
If such interior doors must be installed, they should be gasketed and equipped with a reliable automatic closer.
There should be no ducts, grilles, or other openings that connect the chemical-storage space to the natatorium.
Otherwise, the proper negative pressure on the natatorium will draw in fumes from the stored chemicals.
If the chemical storage room is part of the natatorium building, the room should have a sealed and impervious
ceiling to prevent fumes from reaching other parts of the building.
Pool chemicals must
be stored in a space other than that in which a DRY-O-TRON® is installed. There should be
no ducts, grilles, gaps, or other openings between the chemical-storage space and a space containing a
DRY-O-TRON®.
Chemical fumes entering a space where combustion devices are located may be a code violation - consult your
local code-enforcement authorities.
Chemical fumes entering the natatorium will cause (a) breathing difficulties with some patrons and (b) corrosion of
all exposed metal equipment.
DECTRON
DRY-O-
TRON®
Equipment Room
(may contain
other equipment)
Natatorium
Pool
Chemical-Storage Room
(separate positive ventilation
from and to the outdoors)
Door to chemical-
storage room should
open to outdoors.
Door should not open
to equipment room or
to natatorium.
Wall-ceiling joint must
be carefully sealed
against air leakage.
Sample
Actual floorplans may vary.
BUILDING
CONSTRUCTION
NOTICE
Risk of corrosion. Can cause property damage.
Pool chemicals are very corrosive and can cause severe property damage. Read and
follow these instructions.
2.31

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 020 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 020 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 020
CategoryController
LanguageEnglish

Related product manuals