DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Maintenance Check Oil Level Operation
Data subject to change without notice.
261
For units without oil-level sight glasses, oil levels cannot be checked.
For units with oil-level sight glasses,
the oil level must
be monitored as part of schedule maintenance.
Be sure that the room temperature is within 4°F (2.2°C) and the relative humidity is within 10% of the unit-
nameplate values. Check the oil level after 30 minutes of compressor operation.
The oil level should be as near the middle of the sight glass as possible,
and in any case between 1/4 and 3/4 full.
If the oil level is incorrect after 30 minutes of compressor operation, contact a Dectron-certified technician.
Risk of compressor damage.
DO
NOT OVERFILL OR UNDERFILL.
Risk of contact with moving parts. Can cause injury or death.
This product contains rotating parts and V-belt drives. Do not approach any moving
parts while electric power is applied to unit. Use only approved devices (e.g. locking
safety switch), to disconnect, lockout, and tagout all sources of electrical energy before
working inside the unit cabinet. Allow adequate time for rotating parts to stop. Follow
all applicable safety regulations.
WARNING
Samples
Actual appearances
may vary.
NOTICE
The oil may appear foamy until 30 minutes after the expansion valve is properly adjusted. After the valve is
adjusted, the oil should not
appear foamy. If the oil appears to be foaming after 30 minutes of operation after the
expansion valve is adjusted, contact Dectron.
OPERATION