EasyManuals Logo

Dectron DRY-O-TRON Supervisaire DSV 020 User Manual

Default Icon
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #309 background imageLoading...
Page #309 background image
Dectron, Inc. March 2012
DECTRON
Owners Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Data subject to change without notice.
309
Diagnostics-Mechanical Service
Low compressor oil
pressure
(continued)
Low condenser pressure
Low oil level in crankcase
Check for and correct any refrigerant leaks.
Assure that proper steps have been taken
to assure oil return. See installation
diagram.
Room air temperature too low
Adjust set point to value shown on unit
nameplate.
High suction pressure
Room air temperature above
normal can cause an increased
load on the evaporator.
Adjust set point to value shown on unit
nameplate.
Room relative humidity above
normal can cause increased load
on the evaporator.
Adjust set point to value shown on unit
nameplate.
A closed evaporator-bypass
damper can cause high air
velocities in the evaporator.
Open the bypass damper whenever the
room air temperature is above 78°F.
Improper duct design can cause
high air velocities in the
evaporator.
See the Installation section of this manual.
Correct duct design as necessary.
Excessive total airflow can cause
high air velocities in the
evaporator.
Set total airflow by test to the value shown
on unit nameplate.
Room humidity too low
Adjust set point to value shown on unit
nameplate.
Assure that outdoor air intake is not
excessive.
Pool temperature too low
Reduce water flow rate slightly until a
reasonable temperature is achieved.
ORI valve (water heating
intensity) incorrectly set
Turn the valve adjustment counter-clock-
wise until spindle is flush with housing.
Turn the valve clockwise approximately 7.5
turns. The condenser pressure will depend
on the refrigerant. Refer to chart in Startup
section.
Insufficient refrigerant in system
Add refrigerant to eliminate bubbles in the
sight glass in all modes.
SYMPTOM POSSIBLE CAUSES CHECKS & CORRECTIONS
Problems not indicated by Supervisaire
®
Controller
8.29

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 020 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 020 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 020
CategoryController
LanguageEnglish

Related product manuals