DECTRON
Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
Data subject to change without notice.
94
Installation Ducts Multiple Units
Where two or more DRY-O-TRON® units must be used for the same room, they should be installed in par-
allel, or have separate duct systems. Where two or more units share a duct, install dampers in the return
and supply ducts to prevent backflow should one unit be off for maintenance.
Do not duct two or more DRY-O-TRON® units in series, unless so instructed in writing by Dectron.
Required Backflow
Dampers
Bullhead Tee
Bullhead Tee
Required Backflow
Dampers
Required heaters,
vibration isolators,
supports, etc., are
not shown.
Sample
Actual appearance
may vary.
Sample
Actual appearance
may vary.
INSTALLATION
NOTICE
Optional Equipment - Multiple units in parallel is an optional arrangement.
4b.16