Dectron, Inc. March 2012
Owners Manual DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Major Airflow Options Product Description
Data subject to change without notice.
13
RETURN AIR
COOLING COIL
REHEAT COIL
SUPPLY BLOWER
RETURN-AIR
FILTERS
BYPASS DAMPER
OUTDOOR-AIR DAMPER
SUMMER
EXHAUST-AIR
DAMPER
WINTER
EXHAUST-AIR
DAMPER
SUPPLY AIR
OUTDOOR AIR
EXHAUST AIR
RETURN
AIR
RETURN AIR
COOLING COIL
REHEAT COIL
SUPPLY BLOWER
RETURN-AIR
FILTERS
BYPASS DAMPER
OUTDOOR-AIR DAMPER
SUMMER
EXHAUST-AIR
DAMPER
WINTER
EXHAUST-AIR
DAMPER
SUPPLY AIR
OUTDOOR AIR
EXHAUST AIR
RETURN
AIR
DRY-O-TRON
®
with
EconoSaver
®
The EconoSaver
®
reduces the amount of
energy needed for heating by recovering heat
with the refrigeration system.
In the summer, room air is exhausted
directly. In winter mode, cold air from the
evaporator is exhausted. The heat removed
from the exhaust air is returned to the
incoming outdoor air in the reheat heat
exchanger. This reduces the energy needed
for heating.
The same amount of return air passes
through the evaporator and the evaporator
bypass.
The outdoor-air intake flow rate can be up
to 15% (or up to 35% with air-conditioning
option) of the total supply airflow rate,
depending on outdoor temperature. The
incoming outdoor air must be heated (by
others) to not less than 32°F (0°C). There
may be limitations on maximum flow rates.
See subsequent page in this manual.
DESCRIPTION
1.8