Dectron, Inc. March 2012
Owners Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Testing, Adjusting, and Balancing T.A.B.
Data subject to change without notice.
169
Page
Safety 5.2
Check Air Filters 5.4
Remove Blower Shipping Blocks 5.7
Check Blower Belts 5.8
Relevant Manual Appendices 5.10
Determine Damper Types 5.11
Prepare to Run Blower 5.12
Apply Electric Power 5.13
Controller Interface 5.14
(NO LINK) Interface Addressing 5.15
Set Air Dampers 5.16
Enable Blower(s) 5.19
Voltage Monitor 5.21
Check Blower Rotation 5.24
Optional Blower-Mount Isolators 5.25
Locate Airflow Measurement Plane 5.26
Determine Allowable
Outdoor-Air Intake Rate 5.27
Set Airflows 5.28
Set Pool-Water Flow(s) 5.29
Set Optional Cooling-Water Flow 5.30
Set Optional Cooling-Water Flow Switch 5.32
Set Optional Drycooler Flow 5.33
Set Optional Heating-Water or Steam Flow 5.35
Return Occupied Selection to Clock 5.36
Stop Blowers 5.37
Checklist 5.38
Risk of property damage.
This unit is not a convenience air conditioner - it is a process dehumidifier that is
closely sized to the expected load. Any errors in installation, balancing, or startup will be
obvious in operation.
Improper flows may result in damage to the equipment, unexpected condensation in the
building leading to damage, or monetary losses due to failure to reclaim energy.
The flows must be measured and set within 10% of the stated values.
NOTICE
The information presented in this section represents Dectron’s best effort as of the time
of issue. Compliance with the requirements and recommendations in this section should
produce a correct airflow.
Where any steps are not clear, Dectron offers technical assistance at 1-800-667-6338 or
1-800-676-2566.
Dectron does not warrant that this information is complete for any particular application.
In some cases job-specific requirements may cause factory modifications which may not
appear in this section. Such modifications will be documented in addenda.
Follow all applicable safety rules and regulations, and all applicable codes. Where any
recommendation in this manual conflicts with legal requirements, the legal requirements
take precedence.
Dectron, Inc. does not engage in Test, Adjust, and Balance contracting. All costs, risks,
and responsibilities of testing, adjusting, and balancing are borne by others.
NOTICE
T.A.B.
Product Description 1
Building Design and Construction 2
Receiving, Unloading, Lifting, & Locating 3
Installation 4
Pre-Assembly 4a
Air Distribution, Ventilation, & Ducts 4b
Piping 4c
Wiring 4d
Testing, Adjusting, and Balancing 5
Startup 6
Operation and Maintenance 7
Service 8
5.1