EasyManua.ls Logo

Dectron DRY-O-TRON Supervisaire DSV 040 - Page 304

Default Icon
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dectron, Inc. March 2012
DECTRON
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
Data subject to change without notice.
304
Service Diagnostics - Mechanical
Problems not indicated by Supervisaire
®
Controller
SYMPTOM POSSIBLE CAUSES CHECKS & CORRECTIONS
Unit not cooling
(continued)
Wrongly adjusted head pressure
bypass valve (ORI-6 5/8)
(continued)
Compressor will
not start
No demand
Adjust the set points to the values on the
unit nameplate.
Anti-short-cycle timer prevents
startup for 3 minutes.
Wait.
Compressor overload is turned
off or has tripped (three-phase
units only)
Turn the overload on (where so equipped).
Compressor thermal protector is
open
Allow one hour for compressor to cool.
Open water-pressure switch
circuit
Check circuit continuity. Check for water
flow. Check pressure switch adjustment.
Loose control or power wiring
Check for electrical continuity under load.
Water exit temperature above
120°F
Check the water flow rate.
Clear the fault code.
Closed isolation valves for
outdoor condenser
Check position of ball valves.
Open valves.
Defective relay on S5 relay board
Check whether the A/C three-way valve is
energized.
Replace defective relay.
Room load exceeds the cooling
capacity of the unit
Check the air temperature differential through
the DRY-O-TRON®.
If the differential is 8°F - 10°F (4.5°C - 5.5°C)
the unit is cooling properly.
Check controller
status messages.
4. To adjust this valve, close it
completely and then open it one
turn.
Replace defective valve.
8.24

Related product manuals