EasyManuals Logo

DeDietrich ZENA MS 24 MI FF User Manual

DeDietrich ZENA MS 24 MI FF
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
82
71.06952.02 - EN
INSTALLATION INSTRUCTIONS
19. GAS CONVERSION
The authorised Technical Assistance Service can convert this boiler to natural gas (G. 20) or liquid gas (G.31).
Carry out the following operations:
A) replace the nozzles of the main burner and the gas diaphragm (if tted);
B) new max. and min. calibration of the pressure regulator.
A) Replace the burner nozzles
rDBSFGVMMZQVMMUIFNBJOCVSOFSPGGJUTTFBU
rSFQMBDFUIFNBJOCVSOFSOP[[MFTNBLJOHTVSFUPGVMMZUJHIUFOUIFNUPQSFWFOUHBTMFBLT/P[[MFEJBNFUFSTBSFTQFDJàFE
in table 2.
B) Calibrate the pressure regulator
rDPOOFDUUIFQPTJUJWFQSFTTVSFUFTUQPJOUPGBEJGGFSFOUJBMQSFTTVSFHBVHFQPTTJCMZXBUFSPQFSBUFEUPUIFHBTWBMWF
pressure test point (Pb) (Figure 10). Only for models with sealed chambers, connect the negative pressure test point of
the manometer to a “T” tting in order to join the boiler adjustment outlet, the gas valve adjusting outlet (Pc) and the
pressure gauge. (The same measurement can be made by connecting the pressure gauge to the pressure test point
(Pb) after removing the front panel of the sealed chamber);
Measuring burner pressure using methods other than those described could lead to incorrect results as the low pressure
created by the fan in the sealed chamber would not be taken into account.
B1) Adjustment to nominal heat output:
rPQFOUIFHBTUBQBOETXJUDIUIFCPJMFSUPUIF8JOUFSNPEF
rPQFOBIPUXBUFSUBQUIBUDBOQSPWJEFBáPXSBUFPGBUMFBTUMJUSFTBNJOVUFPSNBLFTVSFUIFSFJTNBYJNVNIFBU
demand;
rSFNPWFUIFNPEVMBUPSDPWFS
rBEKVTUUIFUVCFCSBTTTDSFXBVOUJMUIFQSFTTVSFWBMVFTTIPXOJOUBCMFBSFPCUBJOFE
make sure that the dynamic inlet pressure of the boiler, measured at the gas valve pressure test point (Pa) (Figure 10) is
correct (37 mbar for propane or 20 mbar for natural gas).
B2) Adjustment to reduced heat output:
rEJTDPOOFDUUIFNPEVMBUPSQPXFSDBCMFBOEVOTDSFXUIFTDSFXCVOUJMBQSFTTVSFWBMVFDPSSFTQPOEJOHUPSFEVDFEIFBU
output is achieved (see tab. 1);
rSFDPOOFDUUIFDBCMF
rNPVOUUIFNPEVMBUPSDPWFSBOETFBM
B3) Final checks
rBUUBDIUIFBEEJUJPOBMQMBUFTVQQMJFEXJUIUIFUSBOTGPSNFSTQFDJGZJOHUIFUZQFPGHBTBOEUIFDBMJCSBUJPOQFSGPSNFE
Figure 10
gas valve
mod. SIGMA 845
b
a
0605_1502
Figure 11
CG_2273 / 1008_2602
gas diaphragm
ATTENTION
If the natural gas inlet pressure is too low (less than 17 mbar) remove the gas diaphragm installed over the gas valve (g.
10) and set parameter ' on the electronic board (§21).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DeDietrich ZENA MS 24 MI FF and is the answer not in the manual?

DeDietrich ZENA MS 24 MI FF Specifications

General IconGeneral
BrandDeDietrich
ModelZENA MS 24 MI FF
CategoryBoiler
LanguageEnglish

Related product manuals