2 SPECIFICATION
2.1 STORAGE TEMPERATURE
-40 ºC +85 ºC (-40 ºF +185 ºF )
2.2 OPERATING TEMPERATURE
-30 ºC +70 ºC (-22 ºF +158 ºF )
2.3 REQUIREMENTS FOR UL
WARNING!: More than one live circuit exists, refer to section entitled Typical Wiring
Diagram elsewhere in this document
Screw Terminal
Tightening Torque
Terminals suitable for connection of conductor size AWG 20 to AWG 13
(0.5 mm² to 2.5 mm²).
Conductor protection must be provided in accordance with NFPA 70,
Article 240
Low voltage circuits (35 V or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit conductors
shall be separated and secured to maintain at least ¼” (6 mm) separation
from the generator and mains connected circuit conductors unless all
conductors are rated 600 V or greater.
Must be connected through UL Listed or Recognized isolating current
transformers with the secondary rating of 5 A max.
Must be connected to communication circuits of UL Listed equipment
Suitable for use in type 1 Enclosure Type rating with surrounding air
temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
Suitable for pollution degree 3 environments when voltage sensing inputs
do not exceed 300 V. When used to monitor voltages over
300 V device to be installed in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment.
-22 ºF to +158 ºF (-30 ºC to +70 ºC)
-40 ºF to +176 ºF (-40 ºC to +80 ºC)