9. Troubleshooting
9.1 Troubleshooting for Multi-line 2 and Uni-line products
9.1.1 Remedy of problem
The troubleshooting table can be used for the Uni-line and the Multi-line 2 products.
Problem indication Problem cause Remedy
Load sharing or fixed power control (base
load) unstable.
Synchronisation OK.
Single generator running frequency control
OK.
No speed droop on gener-
ators.
Apply 3-4% speed drop on
prime mover governor.
Load sharing or fixed power voltage (VAr)
control unstable.
Synchronisation OK.
Single generator running frequency control
OK.
No voltage droop on gen-
erators.
Apply 3-4% voltage drop on
generator AVR.
Generator not able to take load to 100%. Initial setting of speed gov-
ernor not correct.
See chapters regarding gover-
nor/AVR checks.
Generator not able to take load to 100%. Analogue output from DE-
IF equipment has too low
output range.
Increase the full scale value.
This is mostly a case when us-
ing electronic potentiometers.
Speed decreases when increase was ex-
pected (relay outputs).
Relay outputs "up" and
"down" reversed.
Swap connections.
Speed decreases when increase was ex-
pected (analogue output).
Outputs "+" and "-" re-
versed.
Swap connections.
Engine overspeeds when starting up. Regulator output is too
high.
Decrease the analogue output
signal by decreasing the resis-
tor.
General guidelines for commissioning
4189340703 UK
Troubleshooting
DEIF A/S Page 25 of 25

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif AGC 200 Series and is the answer not in the manual?

Deif AGC 200 Series Specifications

General IconGeneral
BrandDeif
ModelAGC 200 Series
CategoryController
LanguageEnglish

Related product manuals