The binary inputs use fixed signals. Only the mode shift input and the test input (if the timer is
used) use pulse signal.
4.3 Breaker selection
4.3.1 Breaker selection
The controller can handle pulse, continuous and compact breakers. Selection of the breaker type is done in
the application configuration with the PC utility software. Output for breaker handling is chosen in the I/O con-
figuration of the PC utility software. In the table below is listed which outputs are needed for breaker handling
depending on the breaker type.
Breaker type GB on/MB on/TB on GB off/MB off/TB off
Pulse breaker X X
Continuous breaker X
Compact breaker X X
The pictures below are examples of how to set up breakers.
CGC 400 installation instructions